Cabling Standards

Data supplied by Fluke Corp.


Standards used by Chemistry IT Centre Networking Team

TIA CAT5 CHANNEL
TIA CAT5 BASIC LINK
TIA CAT3 CHANNEL
TIA CAT3 BASIC LINK

  Definition of Basic Link and Channel

Basic Link
The "Basic Link" configuration is intended for use by cable installers and contractors, testing the fixed wiring in a building. A Basic Link may consist of up to 90 meters of horizontal cable, only one transition connector on each end of the horizontal cable, and two Test Equipment Cords with a length of no more than 2 meters each.


Channel

A "Channel" configuration is intended for LAN owners and LAN systems designers to test the end-to-end connections of their LAN cabling. A Channel may consist of up to 90 meters of horizontal cable, one or two transition connectors on each end of the horizontal cable, and up to 10 meters of user patch cables for a total maximum length of 100 meters. The user's patch cables are used to make the connection to the networking hardware, such as the HUB to Patch Panel and Workstation to Wall Outlet connections.

 

TIA CAT5 CHANNEL
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

69
 
 
 
 

69

100
 
 
 
 

100

85-115
 
 
 
 

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 100m

328ft

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

60.0

50.6

45.6

44.0

40.6

39.0

37.4

35.7

30.6

27.1

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

2.5

4.5

6.3

7.0

9.2

10.3

11.4

12.8

18.5

24.0

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 5 Channel Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 31.25MHz and 250kHz steps from 31.26MHz to 100MHz. 

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 100MHz. 

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 

TIA CAT5 BASIC LINK
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

69
 
 
 
 

69

100
 
 
 
 

100

85-115
 
 
 
 

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 94m

308ft

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

60.0

51.8

47.1

45.5

42.3

40.7

39.1

37.6

32.7

29.3

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

2.1

4.0

5.7

6.3

8.2

9.2

10.3

11.5

16.7

21.6

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 5 Basic Link Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 31.25MHz and 250kHz steps from 31.26MHz to 100MHz.

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 100MHz. 

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 

TIA CAT4 CHANNEL
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4
 
 

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

69

66
 
 

69

69

100

100
 
 

100

100

85-115

85-115
 
 

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 100m

328ft

1.0

4.0

8.0

10.0

16.0

20.0

53.3

43.3

38.2

36.6

33.1

31.4

1.0

4.0

8.0

10.0

16.0

20.0

2.6

4.8

6.7

7.5

9.9

11.0

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 4 Channel Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 20MHz.

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 20MHz.

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 
 
 

TIA CAT4 BASIC LINK
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4
 
 

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

69

66
 
 

69

69

100

100
 
 

100

100

85-115

85-115
 
 

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 94m

308ft

1.0

4.0

8.0

10.0

16.0

20.0

54.7

45.1

40.2

38.6

35.3

33.7

1.0

4.0

8.0

10.0

16.0

20.0

2.2

4.3

6.0

6.8

8.8

9.9

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 4 Basic Link Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 20MHz.

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 20MHz.

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 

TIA CAT3 CHANNEL
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

69

66

62

69

69

60

100

100

100

100

100

100

85-115

85-115

85-115

85-115

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 100m

328ft

1.0

4.0

8.0

10.0

16.0

39.1

29.3

24.3

22.7

19.3

1.0

4.0

8.0

10.0

16.0

4.2

7.3

10.2

11.5

14.9

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 3 Channel Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 16MHz.

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 16MHz.

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 

TIA CAT3 BASIC LINK
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

69

66

62

69

69

60

100

100

100

100

100

100

85-115

85-115

85-115

85-115

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 94m

308ft

1.0

4.0

8.0

10.0

16.0

40.1

30.7

25.9

24.3

21.0

1.0

4.0

8.0

10.0

16.0

3.2

6.1

8.8

10.0

13.2

N/A N/A N/A N/A
NOTE:

All limits derived from TIA TSB-67 Cat 3 Basic Link Specifications. 

Above stated NEXT and Attenuation limits are a summary. Refer to TSB-67 for the formulas used to compute limits at other frequencies.

Minimum required frequency step size for NEXT is 150kHz steps from 1MHz to 16MHz.

Minimum required frequency step size for Attenuation is 1MHz steps from 1MHz to 16MHz.

The DSP-100 measures and verifies NEXT and Attenuation in 100kHz steps.


 
 
 

ISO/IEC Class A
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

ScTP 120 Ohm Cat 5

ScTP 120 Ohm Cat 4

ScTP 120 Ohm Cat 3

STP 150 Ohm

69

66

62

69

69

60

69

69

60

78

100

100

100

100

100

100

120

120

120

150

N/A 12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

£ 560 3000meters

9843 feet

0.1 27.0 0.1 16.0 N/A N/A N/A N/A
NOTE:

All limits derived from ISO/IEC IS-11801 Specifications.

Maximum length is limited to DSP-100 to Remote communication capability which is typically ~160 meters maximum. 


 

ISO/IEC Class B
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

ScTP 120 Ohm Cat 5

ScTP 120 Ohm Cat 4

ScTP 120 Ohm Cat 3

STP 150 Ohm

69

66

62

69

69

60

69

69

60

78

100

100

100

100

100

100

120

120

120

150

85-115

85-115

85-115

85-115

85-115

85-115

105-135

105-135

105-135

135-165

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

£ 170 700 

meters

2297 feet

0.1

1.0

48.0

11.0

0.1

1.0

5.5

15.0

N/A N/A N/A N/A
NOTE:

All limits derived from ISO/IEC IS-11801 Specifications.

NEXT and Attenuation is measured in 100kHz steps (0.1MHz to 1MHz) with limits derived from interpolation from specified limits.

Maximum length is limited to DSP-100 to Remote communication capability which is typically ~160 meters maximum. 


 

ISO/IEC Class C
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

ScTP 120 Ohm Cat 5

ScTP 120 Ohm Cat 4

ScTP 120 Ohm Cat 3

STP 150 Ohm

69

66

62

69

69

60

69

69

60

78

100

100

100

100

100

100

120

120

120

150

85-115

85-115

85-115

85-115

85-115

85-115

105-135

105-135

105-135

135-165

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

£ 40 160 m

525 ft

1.0

4.0

10.0

16.0

39.0

29.0

23.0

19.0

1.0

4.0

10.0

16.0

3.7

6.6

10.75

14.0

N/A N/A 1.0

10.00

10.01

16.0

18.0

18.0

15.0

15.0

NOTE:

All limits derived from ISO/IEC IS-11801 Specifications.

NEXT, Attenuation, and Return Loss is measured in 100kHz steps (1MHz to 16MHz) with limits derived from interpolation from specified limits.


 
 
 

ISO/IEC Class D
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

ScTP 120 Ohm Cat 5

STP 150 Ohm

2 PR UTP Wire Map 
 
 

2 PR ScTP and STP Wire Map

69
 
 
 
 

69

69

78

100
 
 
 
 

100

120

150

85-115
 
 
 
 

85-115

105-135

135-165

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

12345678S

||||

3456

12345678S

|||| |

3456 S

£ 40 100 m

328 ft

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

54.0

45.0

39.0

36.0

34.5

31.5

27.0

24.0

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

2.5

4.8

7.5

9.4

10.5

13.1

18.4

23.2

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

40.0

40.0

35.0

30.0

28.0

23.0

13.0

4.0

1.0

10.00

10.01

20.00

20.01

100.0

18.0

18.0

15.0

15.0

10.0

10.0

NOTE:

All limits derived from ISO/IEC IS-11801 Specifications.

NEXT, Attenuation, ACR, and Return Loss is measured in 100kHz steps (1MHz to 100MHz) with limits derived from interpolation from specified limits.


 

ISO/IEC Class D - No RL
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

ScTP 120 Ohm Cat 5

STP 150 Ohm

2 PR UTP Wire Map 
 
 

2 PR ScTP and STP Wire Map

69
 
 
 
 

69

69

78

100
 
 
 
 

100

120

150

85-115
 
 
 
 

85-115

105-135

135-165

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

12345678S

||||

3456

12345678S

|||| |

3456 S

£ 40 100 m

328 ft

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

54.0

45.0

39.0

36.0

34.5

31.5

27.0

24.0

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

2.5

4.8

7.5

9.4

10.5

13.1

18.4

23.2

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

40.0

40.0

35.0

30.0

28.0

23.0

13.0

4.0

N/A N/A
NOTE:

All tests and limits are the same as standard ISO/IEC Class D except Return Loss is not tested.


 

IEEE 10BaseT
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

69

66

62

69

100

100

100

100

85-111

85-111

85-111

85-111

12345678S

||| |

123 6

12345678S

||| | |

123 6 S

N/A 100m

328ft

5.0

10.0

30.4

26.0

5.0

10.0

11.5

11.5

N/A N/A N/A N/A
NOTE:

All limits derived from IEEE Std 802.3i-1990 Supplement Specifications.

NEXT and Attenuation are measured from 5MHz to 10MHz in 100kHz steps. 

NEXT limit = 26-15log10(f/10) db. f is the frequency in MHz over the range of 5MHz to 10MHz. 

Attenuation limit is 11.5dB at all frequencies from 5MHz to 10MHz. 


 
 
 

100BaseTX
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5
 
 
 
 

STP 150 Ohm

69
 
 
 
 

69
 
 
 
 

78

100
 
 
 
 

100
 
 
 
 

150

85-115
 
 
 
 

85-115
 
 
 
 

135-165

12345678S

||| |

123 6

12345678S

||| | |

123 6 S

12345678S

|||| |

3456 S

N/A 100m

328ft

1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

40.0

60.0

80.0

51.0

46.6

42.0

39.4

37.6

36.1

34.9

33.0

31.6

27.0

24.4

22.6

16.0 10.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

40.0

60.0

80.0

48.0

43.6

39.0

36.4

34.6

33.1

31.9

30.0

28.6

24.0

21.4

19.6

N/A N/A
NOTE:

All limits derived from from 100Base-TX P802.3DU

NEXT and ACR is measured in 100kHz steps (1MHz to 80MHz) with limits derived from interpolation from specified limits.

Attenuation is a single point (16.0MHz) measurement.


 

100BaseT4
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

69

66

62

69

100

100

100

100

85-115

85-115

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 100m

328ft

12.5 24.5 2.0

12.5

12.5

12.5

N/A N/A N/A N/A
NOTE:

All limits derived from 100Base-T4 P802.3DU 

Attenuation is measured in 100kHz steps from 2MHz to 12.5MHz with the limit of 12.5dB for all frequencies.

NEXT is a single (12.5MHz) frequency point measurement. 


 

IEEE 802.12 4-UTP
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

ScTP 100 Ohm Cat 4

ScTP 100 Ohm Cat 3

69

66

62

69

69

60

100

100

100

100

100

100

85-115

85-115

85-115

85-115

85-115

85-115

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

N/A 100m

328ft

1.0

2.0

4.0

6.0

8.0

10.0

12.0

15.0

45.0

40.5

35.9

33.4

31.5

30.0

28.8

27.4

0.1

15.0

14.0

14.0

N/A N/A N/A N/A
NOTE:

All limits derived from IEEE 802.12

NEXT is measured in 100kHz steps (1MHz to 15MHz) with limits derived from interpolation from specified limits.

Attenuation is measured in 100kHz steps from 0.1MHz to 15.0MHz with a limit of 14.0dB for all frequencies.

IEEE 802.12 STP
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
STP 150 Ohm 78 150 135-165 12345678S

|||| |

3456 S

£ 40 100m

328ft

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

54.0

45.0

39.0

36.0

34.5

31.5

27.0

24.0

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

2.5

4.8

7.5

9.4

10.5

13.1

18.4

23.2

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

40.0

40.0

35.0

30.0

28.0

23.0

13.0

4.0

1.0

10.0

10.01

20.0

20.01

100.0

18.0

18.0

15.0

15.0

10.0

10.0

NOTE:

All limits derived from IEEE 802.12

NEXT, Attenuation, ACR, and Return Loss is measured in 100kHz steps (1MHz to 100MHz) with limits derived from interpolation from specified limits.


 

TOKEN RING, 4Mb/s
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

69

66

62

69

100

100

100

100

85-115

85-115

85-115

85-115

12345678S

||||

3456

12345678S

|||| |

3456 S

N/A 100m

328ft

4.0 15.5 4.0 19.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

26.5

22.0

17.5

14.8

13.0

11.6

10.4

N/A N/A
STP 150 Ohm 78 150 135-165 12345678S

|||| |

3456 S

N/A 100m

328ft

4.0 15.5 4.0 19.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

28.0

23.5

19.0

16.3

14.5

13.1

11.9

N/A N/A
NOTE:

All limits derived from IEEE 802.5q/D7 (ISO/IEC 8802-5.2)

NEXT and Attenuation are a single (4MHz) frequency point measurement. 

ACR is measured in 100kHz steps (1MHz to 12MHz) with limits derived from interpolation from specified limits.


 

TOKEN RING, 16Mb/s, PASSIVE
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4
 
 

ScTP 100 Ohm Cat 5

69

66
 
 

69

100

100
 
 

100

85-115

85-115
 
 

85-115

12345678S

||||

3456

12345678S

|||| |

3456 S

N/A 100m

328ft

16.0 13.5 16.0 19.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

22.0

25.0

33.5

29.1

24.521.9

20.1

18.6

17.4

15.5

14.1

13.4

12.6

N/A N/A
STP 150 Ohm 78 150 135-165 12345678S

|||| |

3456 S

N/A 100m

328ft

16.0 13.5 16.0 19.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

22.0

25.0

35.0

30.6

26.0

23.4

21.6

20.1

18.9

17.0

15.6

14.9

14.1

N/A N/A
NOTE:

All limits derived from IEEE 802.5q/D7 (ISO/IEC 8802-5.2)

NEXT and Attenuation are a single (16MHz) frequency point measurement. 

ACR is measured in 100kHz steps (1MHz to 25MHz) with limits derived from interpolation from specified limits.


 
 
 

TOKEN RING, 16Mb/s, ACTIVE
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5

UTP 100 Ohm Cat 4

UTP 100 Ohm Cat 3

ScTP 100 Ohm Cat 5

69

66

62

69

100

100

100

100

85-115

85-115

85-115

85-115

12345678S

||||

3456

12345678S

|||| |

3456 S

N/A 100m

328ft

16.0 12.0 16.0 16.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

22.0

25.0

32.0

27.6

23.0

20.4

18.6

17.1

15.9

14.0

12.6

11.9

11.0

N/A N/A
STP 150 Ohm 78 150 135-165 12345678S

|||| |

3456 S

N/A 100m

328ft

16.0 12.0 16.0 16.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

22.0

25.0

33.5

29.1

24.5

21.9

20.1

18.6

17.4

15.5

14.1

13.4

12.6

N/A N/A
NOTE:

All limits derived from IEEE 802.5q/D7 (ISO/IEC 8802-5.2)

NEXT and Attenuation are a single (16MHz) frequency point measurement. 

ACR is measured in 100kHz steps (1MHz to 25MHz) with limits derived from interpolation from specified limits.


 

TP-PMD
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

STP 150 Ohm

69
 
 
 
 

69

78

100
 
 
 
 

100

150

85-115
 
 
 
 

85-115

135-165

12345678S

|| ||

78 12

12345678S

|| |||

78 12S

N/A 100m

328ft

1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

40.0

60.0

80.0

51.0

46.6

42.0

39.4

37.6

36.1

34.9

33.0

31.6

27.0

24.4

22.6

16.0 10.0 1.0

2.0

4.0

6.0

8.0

10.0

12.0

16.0

20.0

40.0

60.0

80.0

48.0

43.6

39.0

36.4

34.6

33.1

31.9

30.0

28.6

24.0

21.4

19.6

N/A N/A
NOTE:

All limits derived from TP-PMD/306 Rev. 2.0 Specifications.

Attenuation are a single (16MHz) frequency point measurement. 

NEXT and ACR are measured in 100kHz steps (1MHz to 80MHz) with limits derived from interpolation from specified limits.


 

ALL TEST
 
   
Impedance
Required
Res.
Max
NEXT
Attenuation
ACR
Return Loss
Cable Type
nvp
nom
limit W
Wire Map
W
length
MHz
dB
MHz
dB
MHz
dB
MHz
dB
UTP 100 Ohm Cat 5
 
 
 
 

ScTP 100 Ohm Cat 5

ScTP 120 Ohm Cat 5

STP 150 Ohm

69
 
 
 
 

69

69

78

100
 
 
 
 

100

120

150

85-115
 
 
 
 

85-115

105-135

135-165

12345678S

||||||||

12345678

12345678S

|||||||||

12345678S

 

£ 40 100 m

328 ft

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

60.0

50.6

45.6

44.0

40.6

39.0

37.4

35.7

30.6

27.1

1.0

4.0

8.0

10.0

16.0

20.0

25.0

31.25

62.5

100.0

2.5

4.5

6.3

7.0

9.2

10.3

11.4

12.8

18.5

24.0

1.0

4.0

10.0

16.0

20.0

31.25

62.5

100.0

40.0

40.0

35.0

30.0

28.0

23.0

13.0

4.0

1.0

10.00

10.01

20.00

20.01

100.0

18.0

18.0

15.0

15.0

10.0

10.0

NOTE:

NEXT and Attenuation limits are the same as TIA Cat 5 Channel limits.

ACR and Return Loss limits are the same as ISO/IEC IS 11801 Class D limits.


 

ISO/IEC 8802.3 (1993) 10Base2
 
   
Impedance
DC Res.
Max
Cable Type
nvp
nom
limit W
Limit W
length
10Base2

RG-58

RG-58 Foam

80

66

78

50

50

50

42 - 58

42 - 58

42 - 58

48 - 65

48 - 65

48 - 65

185m

607ft

NOTE:

All limits derived from ISO/IEC 8802.3


 

ISO/IEC 8802.3 (1993) 10Base5
 
   
Impedance
DC Res.
Max
Cable Type
nvp
nom
limit W
Limit W
length
10Base5

RG-8

78

84

50

50

42 - 58

42 - 58

48 - 65

48 - 65

500m

1640ft

NOTE:

All limits derived from ISO/IEC 8802.3


 

Coax Cables
 
   
Impedance
DC Res.
Max
Cable Type
nvp
nom
limit W
Limit W
length
10Base2

10Base5

RG-58

RG-58 Foam

RG-8

RG-8A/U

RG-59

RG-59 Foam

RG-62

80

78

66

78

84

84

78

78

84

50

50

50

50

50

52

75

75

93

42 - 58

42 - 58

42 - 58

42 - 58

42 - 58

44 - 60

67 - 83

67 - 83

85 - 101

48 - 65

48 - 65

48 - 65

48 - 65

48 - 65

50 - 67

70 - 89

70 - 89

90 - 110

500m

1640ft

NOTE:

Coax Cables: is a generic cable test for coaxial cables. Impedance and resistance limits are defined by the cable type. Maximum length is 500 meters.


 

ARCnet
 
   
Impedance
DC Res.
Max
Cable Type
nvp
nom
limit W
Limit W
length
RG-62 84 93 85 - 101 90 - 110 500m

1640ft

NOTE: